a. First close the suction stop valve of the refrigeration compressor. Start the compressor and discharge refrigerant inside the crankcase into the condenser.
To avoid liquid slugging during this process, start and stop the compressor intermittently several times.
Shut down the unit once the internal pressure of the compressor approaches atmospheric pressure, then close the discharge stop valve.
b. Remove the plug of the oil filler port. Attach a funnel and pour oil into the filler port until the oil level reaches the specified oil line, then stop filling.a. Close the compressor suction stop valve and start the refrigeration compressor. Discharge refrigerant in the crankcase into the condenser,
then shut down the compressor and close the discharge stop valve. Remove the screw plug on the bypass port of the discharge stop valve to vent residual gas inside the high-pressure chamber. Next,
remove the screw plug on the bypass port of the suction stop valve, and install a tapered threaded connector and copper pipe.
b. Block the oil suction pipe opening with a finger and start the compressor to evacuate air from the crankcase.
Stop the compressor when a strong suction force is felt on the finger, indicating the crankcase has reached a vacuum state.
c. Place the oil suction pipe into prepared refrigeration oil and release the finger to start oil suction. Stop filling once the oil level reaches the normal range.Name: Nancy